Study of Oil/Pressboard Creeping Discharges under Divergent AC Voltage—Part 1: Fundamental Phenomena and Influencing Factors

Research output: Contribution to journalArticleResearchpeer review

Authors

View graph of relations

Details

Original languageEnglish
Article number9405769
Pages (from-to)355 - 363
Number of pages9
JournalIEEE Transactions on Dielectrics and Electrical Insulation
Volume28
Issue number2
Publication statusPublished - 15 Apr 2021

Abstract

This paper presents an experimental study of the fundamental phenomena of progressive creeping discharge as well as the influences of pressboard ageing and voltage amplitude under divergent AC voltages. A ramp-stress test is used to determine the partial discharge inception voltage (PDIV) and the flashover voltage of oil/pressboard interface versus pressboard ageing. Constant-stress tests are carried out to investigate the partial discharge (PD) behaviors, the pressboard surface temperature, and the oil-dissolved gases of progressive creeping discharges. It is found that the pressboard ageing affects only the interface PDIV. The progressive creeping discharges concentrate at the triple-junction and comprises probably oil corona discharges and surface discharges in pressboard dimples. If no pressboard damage is present, the progressive discharges exhibit in general a constant PD pattern but a diminishing intensity, and nevertheless can be sustained for the severely-aged pressboards under strong voltages. The underlying causes are correlated with the competing effects of pressboard ageing on interface moisture and the triple-junction field intensification. Gas analyses indicate the hydrogen is the principal faulty gas and the Duval's Triangle diagnoses the progressive creeping discharges as either low-energy or high-energy discharge fault. No pressboard overheating is observed during the discharges.

Keywords

    aging, creeping discharge, field distribution, flashover, interface phenomena, moisture, partial discharge (PD)

ASJC Scopus subject areas

Cite this

Study of Oil/Pressboard Creeping Discharges under Divergent AC Voltage—Part 1: Fundamental Phenomena and Influencing Factors. / Zhou, Xin; Werle, Peter; Gockenbach, Ernst et al.
In: IEEE Transactions on Dielectrics and Electrical Insulation, Vol. 28, No. 2, 9405769, 15.04.2021, p. 355 - 363.

Research output: Contribution to journalArticleResearchpeer review

Download
@article{caee7c29c5954e129286492137d10266,
title = "Study of Oil/Pressboard Creeping Discharges under Divergent AC Voltage—Part 1: Fundamental Phenomena and Influencing Factors",
abstract = "This paper presents an experimental study of the fundamental phenomena of progressive creeping discharge as well as the influences of pressboard ageing and voltage amplitude under divergent AC voltages. A ramp-stress test is used to determine the partial discharge inception voltage (PDIV) and the flashover voltage of oil/pressboard interface versus pressboard ageing. Constant-stress tests are carried out to investigate the partial discharge (PD) behaviors, the pressboard surface temperature, and the oil-dissolved gases of progressive creeping discharges. It is found that the pressboard ageing affects only the interface PDIV. The progressive creeping discharges concentrate at the triple-junction and comprises probably oil corona discharges and surface discharges in pressboard dimples. If no pressboard damage is present, the progressive discharges exhibit in general a constant PD pattern but a diminishing intensity, and nevertheless can be sustained for the severely-aged pressboards under strong voltages. The underlying causes are correlated with the competing effects of pressboard ageing on interface moisture and the triple-junction field intensification. Gas analyses indicate the hydrogen is the principal faulty gas and the Duval's Triangle diagnoses the progressive creeping discharges as either low-energy or high-energy discharge fault. No pressboard overheating is observed during the discharges.",
keywords = "aging, creeping discharge, field distribution, flashover, interface phenomena, moisture, partial discharge (PD)",
author = "Xin Zhou and Peter Werle and Ernst Gockenbach and Shi, {Hui Bin} and Moritz Kuhnke",
note = "Funding Information: The first author would like to thank the Chinese Scholarship Council for sponsoring his Ph.D. program. Our grateful thanks are also due to Dr. Woche and Mr. Klatt from the Institut f{\"u}r Bodenkunde of Leibniz University of Hannover for their warm-hearted assistance in the microscope measurements.",
year = "2021",
month = apr,
day = "15",
doi = "10.1109/tdei.2020.009196",
language = "English",
volume = "28",
pages = "355 -- 363",
journal = "IEEE Transactions on Dielectrics and Electrical Insulation",
issn = "1070-9878",
publisher = "Institute of Electrical and Electronics Engineers Inc.",
number = "2",

}

Download

TY - JOUR

T1 - Study of Oil/Pressboard Creeping Discharges under Divergent AC Voltage—Part 1: Fundamental Phenomena and Influencing Factors

AU - Zhou, Xin

AU - Werle, Peter

AU - Gockenbach, Ernst

AU - Shi, Hui Bin

AU - Kuhnke, Moritz

N1 - Funding Information: The first author would like to thank the Chinese Scholarship Council for sponsoring his Ph.D. program. Our grateful thanks are also due to Dr. Woche and Mr. Klatt from the Institut für Bodenkunde of Leibniz University of Hannover for their warm-hearted assistance in the microscope measurements.

PY - 2021/4/15

Y1 - 2021/4/15

N2 - This paper presents an experimental study of the fundamental phenomena of progressive creeping discharge as well as the influences of pressboard ageing and voltage amplitude under divergent AC voltages. A ramp-stress test is used to determine the partial discharge inception voltage (PDIV) and the flashover voltage of oil/pressboard interface versus pressboard ageing. Constant-stress tests are carried out to investigate the partial discharge (PD) behaviors, the pressboard surface temperature, and the oil-dissolved gases of progressive creeping discharges. It is found that the pressboard ageing affects only the interface PDIV. The progressive creeping discharges concentrate at the triple-junction and comprises probably oil corona discharges and surface discharges in pressboard dimples. If no pressboard damage is present, the progressive discharges exhibit in general a constant PD pattern but a diminishing intensity, and nevertheless can be sustained for the severely-aged pressboards under strong voltages. The underlying causes are correlated with the competing effects of pressboard ageing on interface moisture and the triple-junction field intensification. Gas analyses indicate the hydrogen is the principal faulty gas and the Duval's Triangle diagnoses the progressive creeping discharges as either low-energy or high-energy discharge fault. No pressboard overheating is observed during the discharges.

AB - This paper presents an experimental study of the fundamental phenomena of progressive creeping discharge as well as the influences of pressboard ageing and voltage amplitude under divergent AC voltages. A ramp-stress test is used to determine the partial discharge inception voltage (PDIV) and the flashover voltage of oil/pressboard interface versus pressboard ageing. Constant-stress tests are carried out to investigate the partial discharge (PD) behaviors, the pressboard surface temperature, and the oil-dissolved gases of progressive creeping discharges. It is found that the pressboard ageing affects only the interface PDIV. The progressive creeping discharges concentrate at the triple-junction and comprises probably oil corona discharges and surface discharges in pressboard dimples. If no pressboard damage is present, the progressive discharges exhibit in general a constant PD pattern but a diminishing intensity, and nevertheless can be sustained for the severely-aged pressboards under strong voltages. The underlying causes are correlated with the competing effects of pressboard ageing on interface moisture and the triple-junction field intensification. Gas analyses indicate the hydrogen is the principal faulty gas and the Duval's Triangle diagnoses the progressive creeping discharges as either low-energy or high-energy discharge fault. No pressboard overheating is observed during the discharges.

KW - aging

KW - creeping discharge

KW - field distribution

KW - flashover

KW - interface phenomena

KW - moisture

KW - partial discharge (PD)

UR - http://www.scopus.com/inward/record.url?scp=85104667200&partnerID=8YFLogxK

U2 - 10.1109/tdei.2020.009196

DO - 10.1109/tdei.2020.009196

M3 - Article

VL - 28

SP - 355

EP - 363

JO - IEEE Transactions on Dielectrics and Electrical Insulation

JF - IEEE Transactions on Dielectrics and Electrical Insulation

SN - 1070-9878

IS - 2

M1 - 9405769

ER -