Abstract
In this paper the measuring results of polarisation and depolarisation current (PDC) on oil-pressboard samples will be presented. The samples have been aged at 115°C with 3 mg/l of powder of Fe, Cu and Zn as catalyst in order to simulate the stress conditions in a power transformer. Four aged samples have provided for 250, 500, 1000, 2000 hours ageing. Tests have been made also on four moisturised samples. Depolarisation current curves are decomposed to basic exponential functions. Obtained results show differences between aged and moisturised samples, which means that the applied method can distinguish between influences of thermal ageing and water contents.
ASJC Scopus Sachgebiete
- Ingenieurwesen (insg.)
- Elektrotechnik und Elektronik
Zitieren
- Standard
- Harvard
- Apa
- Vancouver
- BibTex
- RIS
in: ETG-Fachberichte (Energietechnische Gesellschaft im VDE), Nr. 97, 2004, S. 287-290.
Publikation: Beitrag in Fachzeitschrift › Konferenzaufsatz in Fachzeitschrift › Forschung › Peer-Review
}
TY - JOUR
T1 - PDC Measurement and Analysis On Oil-Pressboard Samples
AU - Shayegani, A. A.
AU - Hassan, O.
AU - Farahani, M.
AU - Borsi, H.
AU - Gockenbach, E.
AU - Mohseni, H.
PY - 2004
Y1 - 2004
N2 - In this paper the measuring results of polarisation and depolarisation current (PDC) on oil-pressboard samples will be presented. The samples have been aged at 115°C with 3 mg/l of powder of Fe, Cu and Zn as catalyst in order to simulate the stress conditions in a power transformer. Four aged samples have provided for 250, 500, 1000, 2000 hours ageing. Tests have been made also on four moisturised samples. Depolarisation current curves are decomposed to basic exponential functions. Obtained results show differences between aged and moisturised samples, which means that the applied method can distinguish between influences of thermal ageing and water contents.
AB - In this paper the measuring results of polarisation and depolarisation current (PDC) on oil-pressboard samples will be presented. The samples have been aged at 115°C with 3 mg/l of powder of Fe, Cu and Zn as catalyst in order to simulate the stress conditions in a power transformer. Four aged samples have provided for 250, 500, 1000, 2000 hours ageing. Tests have been made also on four moisturised samples. Depolarisation current curves are decomposed to basic exponential functions. Obtained results show differences between aged and moisturised samples, which means that the applied method can distinguish between influences of thermal ageing and water contents.
UR - http://www.scopus.com/inward/record.url?scp=1642313087&partnerID=8YFLogxK
M3 - Conference article
AN - SCOPUS:1642313087
SP - 287
EP - 290
JO - ETG-Fachberichte (Energietechnische Gesellschaft im VDE)
JF - ETG-Fachberichte (Energietechnische Gesellschaft im VDE)
SN - 0341-3934
IS - 97
T2 - Diagnostik Elektrischer Betriebsmittel
Y2 - 9 March 2004 through 10 March 2004
ER -