Details
Originalsprache | Englisch |
---|---|
Publikationsstatus | Veröffentlicht - 1984 |
Abstract
This report covers the activities of two task forces of CIGRE W. G. 15. 02 (Dielectric Liquids) to develop an acceptable partial discharge technique to characterize liquids, and to elucidate the physico-chemical processes in the gassing of liquids and develop a gassing test method. Three partial discharge methods are considered. One uses a coaxial capacitor model. Another uses an impregnated barrier model. The third method uses an all-liquid needle-to-plane gap. Consideration is given to discharge criteria, and to specimen treatment and conditioning. In the studies of gassing, an improved test cell was used which contains a disc shaped bubble in the liquid. A gassing rate was defined, and measurements showed that it is related to the nature of the liquid. Both task forces are continuing their respective activities.
ASJC Scopus Sachgebiete
- Ingenieurwesen (insg.)
- Allgemeiner Maschinenbau
Zitieren
- Standard
- Harvard
- Apa
- Vancouver
- BibTex
- RIS
1984.
Publikation: Konferenzbeitrag › Paper › Forschung › Peer-Review
}
TY - CONF
T1 - BEHAVIOUR OF HIGHLY STRESSED INSULATING LIQUIDS EVALUATED BY PARTIAL DISCHARGE GENERATION AND DEVELOPMENT.
AU - Mandelcorn, L.
AU - Fallou, B.
AU - Nishimatsu, M.
AU - Tobazeon, R.
AU - Kako, Y.
AU - Beyer , Manfred
PY - 1984
Y1 - 1984
N2 - This report covers the activities of two task forces of CIGRE W. G. 15. 02 (Dielectric Liquids) to develop an acceptable partial discharge technique to characterize liquids, and to elucidate the physico-chemical processes in the gassing of liquids and develop a gassing test method. Three partial discharge methods are considered. One uses a coaxial capacitor model. Another uses an impregnated barrier model. The third method uses an all-liquid needle-to-plane gap. Consideration is given to discharge criteria, and to specimen treatment and conditioning. In the studies of gassing, an improved test cell was used which contains a disc shaped bubble in the liquid. A gassing rate was defined, and measurements showed that it is related to the nature of the liquid. Both task forces are continuing their respective activities.
AB - This report covers the activities of two task forces of CIGRE W. G. 15. 02 (Dielectric Liquids) to develop an acceptable partial discharge technique to characterize liquids, and to elucidate the physico-chemical processes in the gassing of liquids and develop a gassing test method. Three partial discharge methods are considered. One uses a coaxial capacitor model. Another uses an impregnated barrier model. The third method uses an all-liquid needle-to-plane gap. Consideration is given to discharge criteria, and to specimen treatment and conditioning. In the studies of gassing, an improved test cell was used which contains a disc shaped bubble in the liquid. A gassing rate was defined, and measurements showed that it is related to the nature of the liquid. Both task forces are continuing their respective activities.
UR - http://www.scopus.com/inward/record.url?scp=0021582155&partnerID=8YFLogxK
M3 - Paper
ER -